- Contact Person : Ms. Ye Sunny
- Company Name : Hangzhou Peritech Dehumidifying Equipment Co., Ltd.
- Tel : 86-0571-88532337
- Fax : 86-0571-88532038
- Address : Zhejiang,Hangzhou,Fengdu Industrial Park, Pingyao Town, Yuhang District,
- Country/Region : China
- Zip : 311115
rotary dehumidifier
Work Principle
ZLB Series Low Humidity Dehumidifier Units
Character
1) Intake air filter, silica gel desiccant wheel, double cold-water heat exchanger;
2) Chain drive;
3) Electric heating by stainless steel tube, or by copper tube aluminum fin;
4)Efficient centrifugal fans, aluminum alloy frame, high pressure polyurethane and double foam layer cabinet, anti-cold bridge, electric multi-protection operation;
5) Reliable PLC control system.
Model Example
ZLB-D-1000
ZLB: low humidity dehumidifier units basic code
D: Rotary regeneration type. D for Electricity, Z for Steam.
1000: Process airflow m3/h
Main Parameters of ZLB Series Low Humidity Dehumidifier
Main Parameters / Model | ZLB-5000 | |
Process Air | Airflow m³/h | 5000 |
Fan Power kW | 4.0 | |
Regeneration Air | Airflow m³/h | 1650 |
Fan Power kW | 1.5 | |
Regeneration Mode | Electrical Heating Power kW | 36 |
Steam Consumption kg/h | 60 | |
Outlet Air | Temperature °C | 22±2 |
Relative Humidity % | ≤20 | |
Drive Motor Power kW | 0.12 | |
Installed Power | Electrical Heating kW | 41.62 |
Steam Heating kW | 5.62 | |
Overall Dimensions | Length mm | 5700 |
Width mm | 1230 | |
Height mm | 2300 | |
Weight kg | 1800 | |
Supporting System Refrigerating Capacity kW | 49.9 | |
Frozen Water Consumption t/h | 8.6 |
Note:
1. Parameter of fresh air: 35°C, 80%
2. The ratio of fresh air is 5% of air output.
3. Output air excess pressure ≥200Pa
4. Supporting system refrigerating capacity and frozen water consumption, you only need to choose one.
rotary dehumidifier